Set up MVX9000 to accept speed and direction ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ 20.03 Default: 01 -> 04 Master Frequency determined by RS485. 20.04 Default: 00 -> 03 Operating commands determined by the RS-485 communication interface. Keypad STOP key is enabled. 50.01 Default: 01 -> 04 Master frequency determined by RS485 50.02 Default: 00 -> 03 Operating commands determined by the RS-485 communication interface. Keypad STOP key is enabled. 90.01 Default: 0 -> 3 Modbus RTU mode, <8,N,2> 90.02 Communication Address Range: 01 to 254 Default: 01 90.03 Default: 01 Baud rate 9600 (data transmission speed: bits / sec) ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ Operationing Registers ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ 0705H 90.06 Communication frequency reference 0.0 to 400.0Hz 0706H 90.07 Communication command Bit 0-1: 00 no function 01 Stop 10 Run 11 JOG + Run Bit 2-3: Reserved Bit 4-5: 00 no function 01 Forward 10 Reverse 11 Change direction Bit 6-15: Reserved ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ HAL Pins ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ Input Frequency Run/Stop Direction